74C068 SH C 500V 27x1 Cu2 K2 EG NA

Descripción

Descripción

Estándares

  • Product
    IEC 60228
  • Test
    IEC 60332-3-23; IEC 60754-1; IEC 61034-2; NF C32-070/C1

Applications

These control cables allow connection to a variety of industrial equipement from control room. Many of them require anti-inductive screen (EMI).

Design

Conductor:
- Stranded (class 2) or flexible (class 5) plain copper
Insulation:
- Zero halogen (SH), cross-linked
Assembling:
- Polyester tape (optional)
Inner sheath:
- Low smoke, zero halogen (LSZH)
- Colour: grey
Screen:
- Copper wire braid (CWB) R ≥ 80 %
Outer sheath:
- Low smoke, zero halogen (LSZH)
- Colour: grey

Core identification

Black cores printed with white numbers
Optional: with G/Y core.

Marking

NEXANS 279  Nber of cores & cross-section Cu EG CST 74 C 068 K2 SH 0.3/0.5 (0.6) kV YYYY  Manufacturing number  + metric marking
 

Características

Características

Características de construcción

Características de construcción

Material del conductor
Plain copper
Type of conductor
Stranded, class 2
Aislamiento
Halogen-free
Cubierta interior
-
Pantalla
Bare copper braid
Cubierta exterior
LSZH
Libre de halógenos
IEC 60754-1; IEC 60754-2

Características dimensionales

Características dimensionales

Sección del conductor
1 mm²
Número de conductores
27
Diámetro del conductor
1,3 mm
Diámetro sobre aislamiento
2,4 mm
Diameter over inner sheath
17,8 mm
Diameter over screen
19,1 mm
Diámetro exterior mínimo
20,8 mm
Diámetro exterior máximo
24,0 mm
Peso aproximado
900 kg/km

Características eléctricas

Características eléctricas

Resistencia máxima del conductor en CC a 20º C
18,1 Ohm/km
Maximum DC resistance of the conductor at 90°C
23,000 Ohm/km
Reactance at 50 Hz
0,1 Ohm/km
Short Circuit Current 0,3 s Max
0,26 kA
Short Circuit Current 1 s Max
0,14 kA
Impedance at 50 Hz
18,1 Ohm
Voltage Drop
36,9 V/A.km
Calorific Power
5,7 MJ/m

Características de uso

Características de uso

Temperatura ambiente de utilización (rango)
-20 ... 60 °C
Densidad de los humos
IEC 61034-2
No propagador del incendio
NF C 32070 C1; IEC 60332-3-24 (cat.B)
Resistencia a interferencias electromagnéticas
Resistencia a radiaciones ultravioletas
Life cycle 60years
Yes
Radiation resistant
Yes
Temperatura máxima del conductor
90 °C
Nuclear Classification
K2

Recursos

Recursos

Documentación

xlsx — 0 B

Selling & delivery Information

Minimum bending radius:

10 x outer diameter
To be doubled during laying operations

Marking

NEXANS 279  Nber of cores & cross-section Cu EG CST 74 C 068 K2 SH 0.3/0.5 (0.6) kV YYYY  Manufacturing number  + metric marking

Contáctanos

Temas sobre los que desea recibir mayor información

Campos requeridos

Por favor revise la data ingresada e intente nuevamente

El correo debe contener este símbolo @

Protección de data personal

Tiene el derecho de rechazar el procesamiento de sus datos personales y/o su uso para propósitos comerciales

¡Gracias!

Gracias por contactarse con nosotros. Nos pondremos en contacto pronto.

Error

Ocurrió un error. Por favor intentar nuevamente

Cerrar

Contáctanos

Campos requeridos

Por favor revise la data ingresada e intente nuevamente

El correo debe contener este símbolo @

Protección de data personal

Tiene el derecho de rechazar el procesamiento de sus datos personales y/o su uso para propósitos comerciales

¡Gracias!

Gracias por contactarse con nosotros. Nos pondremos en contacto pronto.

Error

Ocurrió un error. Por favor intentar nuevamente

Cerrar