PV H1Z2Z2-K Energyflex 1x10mm² NR

Description

Description

Standards

  • Product
    EN 50618; IEC 62930

DESIGN

Single core fire resistance solar cable with low smoke, halogen free, crosslinked insulation and sheath.

1. Conductor
   Stranded tinned copper wires class 5 acc. IEC 60228

2. Insulation
   Cross-linked halogen-free rubber
   Colour: white

3. Sheath
   Cross-linked halogen-free fire retardant rubber
   Colour: black

Example of marking: ENERGYFLEX® USE < HAR > H1Z2Z2-K 62930 IEC 131 1 x S mm² 1.5/1.5 (1,8) kV DC lynxeo 269 MADE IN FRANCE Dca

FEATURES

ENERGYFLEX® cables are dedicated to the photovoltaic system direct current (D.C.) side with a nominal D.C. voltage of 1.5 kV and a maximum D.C. voltage of 1.8 kV. Cable suitable to be used with Class II equipment.

These cables are suitable for permanent outdoor long-term use, under variable and harsh climate conditions. They are designed and tested to operate at a normal maximum conductor temperature of 90°C and for 20,000 hours up to 120°C. Therefore, the expected period use is 30 to 40 years under normal usage conditions (lifetime acc. to Arrhenius Diagram).

ENERGYFLEX® cables have a suitable behaviour in water : tests of Annexes D and E of H07RN8F AD8 cables (100 days at 50 °C under 1 kV AC without breakdown), and additional test of 1,5 year in hot water (85°C) under 1 kV DC without breakdown. They are suitable for submerged installations with a maximum cumulated immersion period of 4 months / year.

Characteristics

Characteristics

구조적 특성

구조적 특성

도체 재료
Tin Coated Copper Class 5 acc. To EN 60228
Conductor flexibility
소프트 레벨 5
절연
Cross-linked halogen free rubber
피복
Cross-linked halogen free rubber
Sheath colour
Black (blue or red stripe on request)
색상
검은색
Halogen free
IEC 60754-1; IEC 60754-2
Conductor shape
원형

치수

치수

코어수
1
Nominal outer diameter
7.1 mm
도체 단면적
10 mm²
Approximate net weight
122 kg/km
Minimum outer diameter
6.8 mm
Maximum outer diameter
7.8 mm
Nominal conductor diameter
4 mm
Nominal insulation thickness
0.7 mm
Nominal outer sheath thickness
0.8 mm
도체지름
4.0 mm
무게(근사치)
127 kg/km
외경
- mm

전기적 특성

전기적 특성

Maximum permissible nominal current
70 A
정격전압 Uo/U (Um)
1.0/1.0 (1.2) kV AC 1.5/1.5 (1.8) kV DC
20° C에서 최대 도체 DC저항
1.95 Ohm/km
Maximum DC resistance of the conductor at 90°C
2.330 Ohm/km
Perm current rating in air 30°C
- A
Permissible current rating in air 60°C
98 A
Permissible current rating on a tray 60°C
93 A
Permissible short circuit current conductor 1s
1.3 kA

기계적 특성

기계적 특성

Bending
100 000 cycles in reverse bending
Frequent torsion
100 000 cycles
Mechanical resistance to impacts
Condition AG 2 (medium severity) acc.to HD 60364-5-52
Tensile strength
150 N

사용 특성

사용 특성

操作温度范围
-40 ... 90 °C
Packaging
Drum
Short-circuit max. conductor temperature
250 °C
Gases corrosivity
IEC 60754-2
연기밀도
IEC 61034-1-2
Ozone resistance
EN 50396
Weather resistance
Excellent
난연
IEC 60332-1
Corrosive or Polluting Substances
Condition AF 3 (intermittent accidential) acc. to HD 60364-5-52
Fire retardant
EN 50575
Length
- m
Outdoor Use
Condition AN 3 (high solar radiation), permanent according to EN 50565-1:2014
Resistance to vibrations
Condition AH 3 (sever industrial conditions) acc. to HD 60364-5-52
RoHS conform
RoHS 2011/65/EU
Thermal endurance
IEC 60216-1-2
U.V resistance
EN 50289-4-17 method A, for 720h. Nexans prestige test 4000h
Water proof
Passed 100 days 50°C water immersion test of EN 50525-2-21 annex D and E
최대 운용 온도
120 °C
최소 굽힘 반지름 - 설치 후
23.4 mm

Resources

Resources

Documentation

Declaration of Performance

  • Declaration of Performance n� : 1000199-FRAN
  • Certification Date : 19. 12. 17.
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 1812
  • Declared performance : Dca-s2,d2,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close