NF F 55-625 (K25) 1000V 1x300 B2ca-s1a, d0, a1
NF F 55-625 (K25) 1000V 1x300 B2ca-s1a, d0, a1
- Product ref. : 10278390
- EAN : 3427580774942
Description
Description
Standards
-
ProductEN 50575; EN 60228
-
InstallationNF F 55-625
Application
These cables are used for fixed power or lighting installations (1000 V) and fixed traction circuits (1800 V) in tunnels and underground stations.
Fire performance
- Flame retardant: According to RATP K20 specification
- Fire retardant: According to RATP K20 specification
- Low smoke: According to RATP K20 specification
- Without Halogen: According to RATP K20 specification
- Low Toxicity : According to RATP K20 specification
- Low corrosivity: According to RATP K20 specification
Reaction to fire: B2ca-s1a, d0, a1
Design
- Conductor: Bare copper class 1 or 2
- Insulation: Cross-linked polyethylene (XLPE)
- Outer sheath: Polyolefine without halogen
Colour : black or yellow/green (Y/G)
Core identification
According to NF F 55625
1x: black
COMPLEMENT
Bending Radius
r = 6 x maximum outer diameter
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Type of conductor
Stranded, class 2
Conductor material
Plain copper
Insulation
XLPE (Cross-linked Polyethylene)
Outer sheath
Halogen free polyolefin
Halogen free
IEC/EN 60754-1
Sheath colour
Black
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
300 mm²
Maximum outer diameter
33.0 mm
Approximate weight
3290 kg/km
Usage characteristics
Usage characteristics
Flame retardant
IEC/EN 60332-1-2
Smoke density
IEC 61034-2 & EN 61034-2
Gases corrosivity
IEC/EN 60754-2
Max. conductor temperature in service
90 °C
Operating temperature, range
-20 ... 60 °C
Resources
Resources
Selling & delivery Information
Marking
1000 V cables: 1000 - Nber of cores & cross-section - SH -NF F 55-625 - NEXANS 279 - WW - YY - B2ca-s1a, d0, a1 - Manufacturing n° + metric marking
1800 V cables: 1800 - Nber of cores & cross-section - SH -NF F 55-625 - NEXANS 279 - WW - YY - B2ca-s1a, d0, a1 - Manufacturing n° + metric marking
Declaration of Performance
- Declaration of Performance n� : 1000292-FRME
- Certification Date : 9/18/24
- AVCP (Assessment and Verification of Constancy of Performance) : System 1+
- Notified body : 2658
- Declared performance : B2ca-s1a,d0,a1