EN 50288-7 XLPE Insulation OS Unarmoured 30x2x0,75
EN 50288-7 XLPE Insulation OS Unarmoured 30x2x0,75
- Instrumentation cables 170/300 V
- Overall Screen (OS)
- Oil resistant
Descripción
Descripción
Estándares
-
EnsayoIEC 60332-3-22 Cat.A
Applications
These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control where chemicals may be present.
Design
Conductor:
Stranded bare copper class 2
Insulation:
Cross-linked polyethylene (XLPE)
Overall screen:
Polyester tape
Tinned copper drain wire
Aluminium backed polyester tape
Outer sheath:
Polyvinyl chloride (PVC).
Colour: black.
Other colour on request.
Core identification
Pair: white - black
Quad: white - black - red - blue (2 pair cables assembled as a quad)
White core printed with pair number
Marking
NEXANS 279 XLPE/OA.SCR/PVC 170/300V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking
Standards
EN 50288-7 (Design guide-lines)
Características
Características
Características de construcción
Características de construcción
Características dimensionales
Características dimensionales
Características eléctricas
Características eléctricas
Características de uso
Características de uso
Recursos
Recursos
Documentación
Selling & delivery Information
Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations
Tinned copper conductors available on request