EN 50288-7 XLPE insulation IOS Unarmoured 30x2x0,75

Descripción

Descripción

Estándares

  • Ensayo
    IEC 60332-3-22 Cat.A

Applications

These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control where chemicals may be present. The individual screening of each pair limits the consequence of crosstalk. 

 

Design

Conductor:

Stranded bare copper class 2

Insulation:

Cross-linked polyethylene (XLPE)

Individual screen

Polyester tape

Tinned copper drain wire, 

Aluminium backed polyester tape

Polyester tape

Overall screen

Polyester tape

Tinned copper drain wire 

Aluminium backed polyester tape

Outer sheath:

Polyvinyl chloride (PVC).

Colour: black.

Other colour on request. 

 

Core identification

Pair:  white - black

White core printed with pair number
 

Marking

NEXANS 279 XLPE/IND.+OA.SCR/PVC 170/300V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

EN 50288-7 (Design guide-lines)

 

Características

Características

Características de construcción

Características de construcción

Material del conductor
Cobre desnudo
Type of conductor
Stranded, class 2
Aislamiento
XLPE
Individual screen
Tinned copper drain wire + aluminium/polyester tape
Overall screen
Tinned copper drain wire + aluminium/polyester tape
Cubierta exterior
PVC
Protección
no

Características dimensionales

Características dimensionales

Número de pares
30
Sección del conductor
0,75 mm²
Diámetro del conductor
1,1 mm
Diámetro sobre aislamiento
1,58 mm
Diámetro exterior mínimo
23,2 mm
Diámetro exterior máximo
25,6 mm
Peso aproximado
899 kg/km

Características eléctricas

Características eléctricas

Tensión nominal de servicio Uo/U
170/300V

Características de uso

Características de uso

No propagador del incendio
EN IEC 60332-3-22 (cat A)
Resistencia a aceites
Resistencia a interferencias electromagnéticas
Temperatura ambiente de utilización (rango)
-20 ... 60 °C
Temperatura máxima del conductor
90 °C
Standard
EN

Recursos

Recursos

Documentación

Selling & delivery Information


Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.


Minimum bending radius:

10 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request

Contáctanos

Temas sobre los que desea recibir mayor información

Campos requeridos

Por favor revise la data ingresada e intente nuevamente

El correo debe contener este símbolo @

Protección de data personal

Tiene el derecho de rechazar el procesamiento de sus datos personales y/o su uso para propósitos comerciales

¡Gracias!

Gracias por contactarse con nosotros. Nos pondremos en contacto pronto.

Error

Ocurrió un error. Por favor intentar nuevamente

Cerrar

Contáctanos

Campos requeridos

Por favor revise la data ingresada e intente nuevamente

El correo debe contener este símbolo @

Protección de data personal

Tiene el derecho de rechazar el procesamiento de sus datos personales y/o su uso para propósitos comerciales

¡Gracias!

Gracias por contactarse con nosotros. Nos pondremos en contacto pronto.

Error

Ocurrió un error. Por favor intentar nuevamente

Cerrar