PV H1Z2Z2-K Energyflex 1x4mm² NR

Description

Description

Standards

  • Product
    EN 50618; IEC 62930

DESIGN

Single core fire resistance solar cable with low smoke, halogen free, crosslinked insulation and sheath.

1. Conductor
   Stranded tinned copper wires class 5 acc. IEC 60228

2. Insulation
   Cross-linked halogen-free rubber
   Colour: white

3. Sheath
   Cross-linked halogen-free fire retardant rubber
   Colour: black

Example of marking: ENERGYFLEX® USE < HAR > H1Z2Z2-K 62930 IEC 131 1 x S mm² 1.5/1.5 (1,8) kV DC lynxeo 269 MADE IN FRANCE Dca

FEATURES

These state-of-art 1.5kV D.C. cross-linked Energyflex® cables offer exceptional performances, easy installation and long-term reliability for solar plant. They link photovoltaic panels for Utility-Scale solar plants or rooftops, and also connect them to the array box (if existing), or potentially to the inverter. They are designed and tested to operate at a normal maximum conductor temperature of 90°C and for 20,000 hours up to 120°C. Therefore, the expected period use is 30 to 40 years under normal usage conditions (lifetime acc. to Arrhenius-Diagram).

  • Single core solar cable with low smoke, halogen free, cross-linked insulation and sheath.
  • String Harness according to IEC 62548 Photovoltaic (PV) arrays - Design requirements.

Recommended Use

  • Renewable Energies; Solar Plants.
  • Intended for permanent use outdoor and indoor. 
  • Installation can be fixed or free movable / free hanging, and also in cable trays and conduits.
  • They are suitable for submerged installations with a maximum cumulated immersion period of 6 months / year.

PV

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Tin Coated Copper Class 5 acc. To EN 60228
Conductor flexibility
Flexible class 5
Insulation
Cross-linked halogen free rubber
Outer sheath
Cross-linked halogen free rubber
Sheath colour
Black (blue or red stripe on request)
Colour
Black
Halogen free
IEC 60754-1; IEC 60754-2
Conductor shape
Circular

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
4 mm²
Nominal outer diameter
5.6 mm
Approximate net weight
61 kg/km
Minimum outer diameter
5.3 mm
Maximum outer diameter
5.9 mm
Conductor diameter
2.5 mm
Nominal insulation thickness
0.7 mm
Nominal outer sheath thickness
0.8 mm
Outer Diameter
- mm

Electrical characteristics

Electrical characteristics

Maximum permissible nominal current
39 A
Rated Voltage Uo/U (Um)
1.0/1.0 (1.2) kV AC 1.5/1.5 (1.8) kV DC
Max. DC resistance of the conductor at 20°C
5.09 Ohm/km
Maximum DC resistance of the conductor at 90°C
5.880 Ohm/km
Perm current rating in air 30°C
- A
Permissible current rating in air 60°C
55 A
Permissible current rating on a tray 60°C
52 A
Permissible short circuit current conductor 1s
0.5 kA

Mechanical characteristics

Mechanical characteristics

Bending
100 000 cycles in reverse bending
Frequent torsion
100 000 cycles
Mechanical resistance to impacts
Condition AG 2 (medium severity) acc.to HD 60364-5-52
Tensile strength
60 N

Usage characteristics

Usage characteristics

Operating temperature, range
-40 ... 90 °C
Max. conductor temperature in service
120 °C
Packaging
Drum
Short-circuit max. conductor temperature
250 °C
Gases corrosivity
IEC 60754-2
Smoke density
IEC 61034-1-2
Ozone resistance
EN 50396
Weather resistance
Excellent
Flame retardant
IEC 60332-1
Corrosive or Polluting Substances
Condition AF 3 (intermittent accidential) acc. to HD 60364-5-52
Length
- m
Minimum Bend Radius - Installed
17.7 mm
Outdoor Use
Condition AN 3 (high solar radiation), permanent according to EN 50565-1:2014
Resistance to vibrations
Condition AH 3 (sever industrial conditions) acc. to HD 60364-5-52
RoHS conform
RoHS 2011/65/EU
Thermal endurance
IEC 60216-1-2
U.V resistance
EN 50289-4-17 method A, for 720h. Nexans prestige test 4000h
Water proof
Passed 100 days 50°C water immersion test of EN 50525-2-21 annex D and E

Resources

Resources

Documentation

Selling & delivery Information

 "Want to know more about the environmental impact of the product during its life cycle ?
Please contact:: sustainable.development@nexans.com and discover the PEPecopassport® declaration available with all the details”

Declaration of Performance

  • Declaration of Performance n� : 1000199-FRAN
  • Certification Date : 12/17/19
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 1812
  • Declared performance : Dca-s2,d2,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close