EN 50288-7 Silicone OS Armoured LC 2x2x1,5
EN 50288-7 Silicone OS Armoured LC 2x2x1,5
- Instrumentation cables 170/300 V
- With lead cover (LC)
- Overall Screen (OS)
- Aliphatic and aromatic hydrocarbons resistant
- Produkt ref. : 10135224
- EAN : 3427580322655
Beschreibung
Beschreibung
Normen
-
TestsIEC 60331; IEC 60332-3-22 Cat.A
Applications
These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control. They are well adapted to underground use in industrial applications, in moist areas, where hydrocarbon and mechanical protection are needed. The lead cover brings an enhanced resistance to aromatics hydrocarbons. They maintain circuit integrity when exposed to fire.
Design
Conductor:
Stranded bare copper class 2
Insulation:
Silicone rubber (Sil)
Overall screen:
Polyester tape
Tinned copper drain wire,
Aluminium backed polyester tape
Inner sheath:
Low Smoke Zero Halogen (LSZH)
Colour: black
Lead sheath
Bedding (intermediate sheath):
Polyvinyl chloride (PVC)
Colour: black
Armour:
Galvanized steel wires (SWA)
Outer sheath:
Polyvinyl chloride (PVC)
Colour: black
Other colour on request.
Core identification
Pair: white - black
Quad: white - black - red - blue (2 pair cables assembled as a quad)
White core printed with pair number
Marking
NEXANS 279 SIL/OA.SCR/LSZH//LC/PVC/SWA/PVC 170/300V Nber of pairs & cross-section Cu IEC 60331 IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking
Standards
EN 50288-7 (Design guide-lines)
Eigenschaften
Eigenschaften
Konstruktionsmerkmale
Konstruktionsmerkmale
Abmessungsmerkmale
Abmessungsmerkmale
Elektrische Eigenschaften
Elektrische Eigenschaften
Mechanische Eigenschaften
Mechanische Eigenschaften
Anwendungsmerkmale
Anwendungsmerkmale
Ressourcen
Ressourcen
Dokumentation
Verkauf & Lieferung Informationen
Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations